NUCON NUCELL®TYPE II ADSORBER TRAY
(United States Patent 4,292,059)
The NUCON
NUCELL® carbon adsorber is designed for high efficiency and leak proof
applications. The adsorber conforms to the ASME AG-1 & N509, AACC Standard
CS-8T, and IES-RP-CC-008-84. These documents are referenced in USNRC Regulatory
Guides of various vintage.
The NUCELL® Adsorber is a unique
design with an inner cage of perforated stainless steel surrounded on 5 sides by
at least 2 inches of carbon. The outer cage has perforated stainless steel on 4
sides with a solid fill cover plate. This design allows flow from 4, rather than
2 faces and the loading of significantly more carbon in the same standard
envelope than other current designs. The additional carbon provides higher
residence time and a lower pressure drop at a given flow rate than the common 2
bed design. solid spacer assemblies and all welded construction, except the fill
cover plate, ensure strict dimensional adherence to applicable standards. The
back plate is riveted on. The 2 inches of carbon between this back plate and the
solid back plate of the inner cage eliminates problems from gas flow leakage
through the pop rivets since all gas flow paths are through a least 2 inches of
carbon. Solid, integral glide angles are provided on all surfaces
to protect the cell during installation or removal.
Each NUCELL®Adsorber Tray is filled to maximum packing density with qualified radioiodine removal adsorbent (see NUCON Bulletin 11B4). The full rear opening permits packing the cell without voids. Typically, dimensions are to ASME AG-1 & N509 and older documents such as AACC CS-8T & IES-RP-CC-008-84. (However, trays are manufactured to dimensions specified by the client.) Each NUCELL®Adsorber Tray is halide leak and pressure drop tested. The maximum allowable halide leakage is < 0.01%.
Each NUCELL®Adsorber Tray is marked with all required data and sealed in polyethylene to prevent contamination during storage.
Standard packing/shipment cartons confirm to ASME AG-1 & ANSI N45.2.2. NUCON is fully licensed by the US NRC for radioiodine testing and offers in-house capability to provide all testing listed in U.S.NRC Regulatory Guide 1.52 (all revisions) as well as related ASTM, ANSI and RDT Standards
| Ask for:
|
|
Drawing No.: P-11760-01 (Standard Type II
Adsorber Tray)
|
|
|
|
| Drawing No.: P-11760-02 (Standard Type II Test Tray
Assembly)
|
|
[Home Page],
[Activated Carbon],
[Filter System Testing Services],
[Testing Instruments]
[Nuclear Power Plant Services],
[Laboratory Testing Services],
[DOE & Defense Facility services],
[Solvent Vapor Recovery Systems],
[Company Profile & Experience],
[Site Map],
[Employment]
NUCON International Inc. All Rights Reserved
|